Description
Datasheet
Product description
Peripheries dedicated to expand number of I/Os of the main ComAp controller
Supports wide range of sensor types and characteristics Connection with the main ComAp controller over CAN bus (up to 200 m length)
Extension modules are compatible with
InteliSysNT BaseBox, InteliSysNTC BaseBox, InteliSys GAS, InteliSysNTC Hybrid, InteliSysNT BaseBox Marine
InteliGenNT, InteliGenNT BaseBox, InteliGenNTC BaseBox Marine
InteliMainsNT, InteliMainsNT BaseBox,
InteliMainsNTC BaseBox
InteliDrive DCU Marine, InteliDrive DCU InteliGen4 200, InteliGen 200, InteliGen 500 G2,
InteliGen 500, InteliGen 1000, InteliLite(3) AMF25,
InteliLite(3) AMF20, InteliLite(3) MRS16, Inteli(3) MRS 11, all controllers from InteliLite 4 family, InteliNeo 6000, InteliNeo 5500, InteliMains 210,
InteliMains 1010.
Key features
Analog input: 8 channels Impulse/RPM input: 1 channel
Order code: I-AIN8
Extension Peripheral Modules
Supported sensors: Pt100, Pt1000 Ni100, Ni1000 (0)4 - 20 mA
± 20 mA
0 - 250 Ω, 0 - 2400 Ω, 0 - 10 kΩ
± 1 V DC, 0 - 10 V DC, 0 - 5 V DC
Lambda probe
Application overview
Peripheral extension module for the controllers CAN bus connectivity
Connects analog sensors (via Analog IN) Connects impulse sensor (via Impulse IN
Technical data
Power supply
Power supply | 8 to 36 V DC |
Power consumption |
35 mA a @ 24 V ÷ 100
mA at 8 V |
Operating conditions
Operating temperature | - 30°C to + 70°C |
Storage temperature | - 40°C to + 80°C |
Operation humidityn | 95% w/o condensation |
Vibrations |
5-25 Hz, ±1.6 mm, 25-100
Hz, a = 4 g |
Shocks | a = 200 m/s2 |
Heat radiation | 3 W |
Analog inputs (not galvanic separated)
Voltage |
range: 0-10V
accuracy: ± 0,25 % of actual value ± 25 mV |
Current |
range: ± 20mA accuracy: ± 0,25 % of actual value ±
50 μA |
Resistance |
range: 0- 10 kΩ accuracy: resistance: ± 0,5 % of actual value + ± 2 Ω_Pt100, Pt1000, Ni100,
Ni1000 ± 2,5°C |
Impulse / RPM input
RPM |
level of signal: 2(6) Vpk-pk ÷ 70 Vpk-pk
frequency range 4 Hz ÷ 10 kHz |
Impulse |
Measurement of pulses by norm DIN 43864 and norm IEC 62053-31–
equipment class A. for flow meter pulses: VHmax = 30 V, Imax=30 mA, Tonmin =10 ms,Toffmin = 10 ms, OC |
General information
Protection | IP20 |
Impulse |
CAN bus is galvanic separated from the measurement and power supply.
All analog inputs are galvanic separated from power supply and CAN bus. Analog inputs are not galvanic separated between channels. |
Reviews
There are no reviews yet.